This program is the HAD-FIRE which calculates the conditions for combustion related reactions of duct burner and general gas burner. 1) Based on exhaust gas temperature at burner exit, 2) Based on fixed fuel gas flowrate. 

          *******************************************************************************
          *  Supplemental Firing Calculator                   2013-00                   *

          *******************************************************************************

   Customer : Project                                                     
   Service  : Exhausting_Gas_Condition                                              
 
  = Burner Conditions(Based after flue gas temp.) =
 
 - Flue Gas Compositions
                     Before                   After
                   (Vol% / Wt%)           (Vol% / Wt%)
  N2             78.03       75.45       76.92       74.84
  O2             20.95       23.14       17.75       19.72
  CO2             0.03        0.05        1.50        2.30
  H2O             0.05        0.03        2.91        1.82
  Ar              0.90        1.24        0.89        1.23
  SO2             0.04        0.09        0.04        0.09
  CO              0.00        0.00        0.00        0.00
 
 Wet flue gas Condition O2(vol%) =   17.74646    
 Acid dew point (SO2-ppm) =   394.2591    
 Acid dew point (SO3-ppm) =   28.20251    
 Acid dew point (degC)    =   127.5335    
 Convertion Ratio (%)     =   7.153294    
 
 - Fuel Compostion (Vol%,Wt%) 
  CH4          94.5600     89.2250
  C2H6          3.4100      6.0309
  C3H8          0.8400      2.1786
  N-C4H10       0.0000      0.0000
  I-C4H10       0.1700      0.5812
  N-C5H12       0.0050      0.0212
  I-C5H12       0.0050      0.0212
  C6H14         0.0000      0.0000
  CO            0.0000      0.0000
  H2            0.0000      0.0000
  N2            0.8300      1.3677
  CO2           0.0050      0.0129
  C             0.0000      0.0000
  S             0.0002      0.0003
  C2H4          0.0000      0.0000
  C3H6          0.0000      0.0000
  N-C4H8        0.1700      0.5610
  C6H6          0.0000      0.0000
  H2O           0.0000      0.0000
  O2            0.0000      0.0000
  H2S           0.0000      0.0000
 
 - Exhuast Gas of Duct Burner Inlet -
Flow Rate                   kg/hr    52873.53
                           Nm3/hr    40904.88
Density                    kg/Nm3      1.2926
Temperature                  degC      500.00

 - Fuel Gas of Duct Burner Inlet -  
Flow Rate                   kg/hr      440.32
                           Nm3/hr      580.51
Density                    kg/Nm3      0.7585
Low Heating Value        kcal/Nm3     8890.47
                          kcal/kg    11721.00

 - Exhuast Gas of Duct Burner Outlet - 
Flow Rate                   kg/hr    53313.85
                           Nm3/hr    41502.72
Density                    kg/Nm3      1.2846
Temperature                  degC      839.83