top of page

HAD-AIR ] Gas-Air Preheater

This program is HAD-AIR which can design the gas-air preheater by calculating heat transfer of exhaust gas and air. The program can calculate the following contents.

  • Tube type  : Bare tube/Solid finned tube

  • Pressure drop : Gas side/Air side

  • Max. temperature of tube side

  • Detail information of heat transfer

  • Acid dew point

  • Multi Gas pass condition

          *******************************************************************************
          *  Thermal Design Calculation of Gas-Air Preheater                            *

          *******************************************************************************

 

Customer : Test01                   

Gas Composition 
CO2(Weight/Volume Fraction)      %     16.6109     11.0000
SO2(Weight/Volume Fraction)      %      0.0000      0.0000
 N2(Weight/Volume Fraction)      %     73.4336     76.0000
H2O(Weight/Volume Fraction)      %      5.5635      9.0000
 O2(Weight/Volume Fraction)      %      4.3920      4.0000
HCL(Weight/Volume Fraction)      %      0.0000      0.0000

GAS FLOW  
Weight                       kg/hr      19504.
Normal Volume               Nm3/hr      15000.
Density                     kg/Nm3      1.3003
Weight                      kg/sec        5.42

AIR FLOW  
Weight                       kg/hr      12819.
Normal Volume               Nm3/hr      10000.
Density                     kg/Nm3      1.2819
Weight                      kg/sec        3.56

GAS SIDE                          
GAS FLOW                     kg/hr      19504.
INLET PRESSURE                mmAq      100.00
OUTLET PRESSURE               mmAq       85.18
PRESSURE DROP                 mmAq       14.82
INLET TEMPERATURE            deg C       200.0
OUTLET TEMPERATURE           deg C       118.4
TEMPERATURE DIFF.            deg C        81.6
FOULING FACTOR        m2-hr-c/kcal      0.0004
AIR SIDE                          
FLUID FLOW                   kg/hr      12819.
INLET PRESSURE                mmAq      500.00
OUTLET PRESSURE               mmAq      451.12
PRESSURE DROP                 mmAq       48.88
INLET TEMPERATURE            deg C        20.0
OUTLET TEMPERATURE           deg C       150.3
TEMPERATURE DIFF.            deg C       130.3
HEAT ABSORBED                   KW      476.89
HEAT ABSORBED              kcal/hr    410336.2
FOULING FACTOR        m2-hr-c/kcal      0.0002
 
Gas Side Velocity                   
Mean Velocity                m/sec        4.59
Air Side Velocity                  
Mean Velocity                m/sec        7.50

Tube metal temperature
1st Max. Tube Temp           deg C       181.0
1st Min. Tube Temp           deg C       156.0
Last Max. Tube Temp          deg C       105.9
Last Min. Tube Temp          deg C        80.9


          *******************************************************************************
          *         Geometry                                                            *


 
GAS SIDE                          
FLOW CONFIGURATION                COUNTER-CURR
TUBE ARRANGEMENT                  SQUARE      
GAS SIDE                          SHLL        
Number of shell passes                       1
Number of tube passes                        4
Width of Gas-Air Preheater      mm      1700.0
Length of Gas-Air Preheater     mm      5000.0
Tube Length(heating tube)       mm      2100.0
Tube Diameter                   mm       50.80
Tube Min Thickness              mm      2.7000
Number of Transverse Tubes                  20
Transverse Spacing              mm      85.000
Number of Longitudinal Rows                 60
Longitudinal Spacing            mm      85.000
Finned Type.(1=No,2=Solid)                   1
Tube Roughness                  mm     0.10000
Surface area(Tube Outside)       m      402.17


          *******************************************************************************
          *         Heat Transfer                                                       *


Surface area(Tube Outside)       m      402.17
UO                    kcal/m2-hr-c       14.62
LMTD                                     71.32
LMTD Correction factor                  0.9782
Correction CMTD               degC       69.77
Gas side heat transf. kcal/m2-hr-c       38.34
Air side heat transf. kcal/m2-hr-c       23.64
Enthapy of Inlet Flue Gas  kcal/kg       47.03
Enth. of Outlet Flue Gas   kcal/kg       25.93
HEAT ABSORBED              kcal/hr    410336.2

 

bottom of page